5. Inspection and recording ​

Note

Teach the inspection points in NETRA first (Substation › Inspection points), on the stops of the route under test, and set the day’s air temperature on the robot.

IDProcedurePass whenResult
I1Run the route; at each stop, watch the camera on the H12.The camera turns to every target; NETRA gets a result for every point, with the thermal and visible images.☐ Pass ☐ Fail
I2Measure one target with the reference thermometer at the same time.The robot’s reading within  ± 2 °C or  ± 2 % of the reference. Robot ______, reference ______☐ Pass ☐ Fail
I3Put the heat source on a target of a point with three regions (phases), about 10 K above the others.The finding is at least warning (similar criterion), the hot region marked.☐ Pass ☐ Fail
I4A partial discharge point, with a source or a known corona.The class and the severity in NETRA match the source (corona: attention).☐ Pass ☐ Fail
I5Inspect on the H12 at a stop point.The point is inspected where the robot stands; the result on the H12 and in NETRA.☐ Pass ☐ Fail
I6During the patrol, the recorder.REC on the H12 and in NETRA; a session folder on the perception host with video and thermal frames.☐ Pass ☐ Fail
I7Recorder on and off from NETRA (Live control).It starts and stops; the session is kept.☐ Pass ☐ Fail